Burglar alarm failure and troubleshooting

Source: https://vedard.com/blog/burglar-alarm-failure-and-troubleshooting
Date: 2020/08/28
Firstly, The central system failure.
1. The central machine can not receive all users alarm information.
Possible causes: telephone line interference is too large, telephone line noise, telephone line short circuited or open circuited, telephone anti-theft switch is turned on, communication failure of the telecommunications bureau, host alarm center communication programming error, center software serial port closure, serial line connection error, serial damage, the failure of the computer itself may lead to the center machine can not receive alarm information.
Solution: check whether there is a short circuit and open circuit on the telephone line, turn off the anti-theft switch on the telephone, check whether the central communication programming of the user-side host is correct, including (center phone number, center communication level, central communication format, user number, reporting options, etc.); Check if the central software is a trial and query the system logs to check the software expiration period.
2. The center machine received alarm information, but can not pop up on the software.
Possible cause: The user information does not exist in the central software. The serial port is closed, the serial line connection error, the serial port damage may cause the center machine to receive the alarm message, but can not pop up on the software.
Solution: Add user information to the central software, open the corresponding serial port, connect the serial line correctly, check whether the serial line interface is damaged.
3. The central machine received the alarm information, but the alarm information can not be uploaded or downloaded.
Possible causes:the central telephone line interference is too large, the telephone line appears short circuit, open circuit, telecommunications bureau communication failure. Forwarding number in the center software is not filled correctly may cause the center machine to receive alarm information, the alarm can not be transmitted up/down.
Solution: Check whether the telephone line interference is too large, the telephone line has a short circuit, open circuit, correctly fill the forwarding number in the center software.

Secondly, the alarm host system failure.
1. The alarm host is armed or forced to armed and the wired detector is triggered, but the host does not alarm.
Possible causes: Wired detector and alarm host connection line error, line short circuit, open circuit, detector supply voltage is insufficient, end-of-line resistance missed or wrong wired, zone properties are not edited or edited error, etc. may lead to the alarm host does not alarm after the detector is triggered.
Solution: Check the cable connection between the detector and the alarm host. Check whether the end-of-line resistor is not connected or wrong connected. Use the meter to test whether the line is short-circuited, open circuit, detector power voltage is stable (cannot be less than 9V) and so on. If the zone is not correctly programmed, should correct it.
2.The alarm host does not alarm after the wireless detector is triggered.
Possible reasons: wireless detector battery power is low. Wireless detector code is not correct, or messy code is learned into the alarm host. The wireless detector learned into the alarm host is not programmed with zone properties, or zone properties are wrong edited. The distance between the wireless detector and the alarm host exceeds the rated transmission distance. There is metal barrier between the wireless detector and the alarm host.
Solution: replace the battery. Re-code the wireless detector to the alarm host. Program the zone properties of the detector zone. Shorten the distance between the wireless detector and the alarm host. If there is a metal barrier between the detector and the alarm host, then re-adjust the detector installation location.
3.The alarm host can not receive high-frequency signal, why? (including remote control and wireless converter)
Possible causes: The remote control battery is low or the converter is not powered on. The wireless code of the remote control and wireless converter is not learned to the alarm host, or is too far away from the host. The host failure to decode etc.
Solution: replace the battery or change a remote control to test, correctly program to learn wireless code, shorten the distance between the remote control and wireless converter and the host. If multiple remote controls can not be learned into the host, that means the alarm host may have problem of high-frequency reception and need to return to manufacturer for repair.

4.The alarm host false alarm.
Possible cause: The possibility of false alarm caused by the alarm host is very low. Because the host is only a signal receiving processor, and even if there are false alarms, most of them are caused by detectors. Unless the voltage fluctuation is too large may lead to host false alarm. When false alarm occurs, please check the detector status.
Solution: First confirm the false alarm zone and detector, and then check the detector.
5.The alarm host is in normal use but it makes a sound without any reason.
Description: The chimes of the host can be divided into beeps, fault chimes, guard exit delay tones, alarms into delay tones.
Solution: Please confirm what kind of chime the host is making. If there is no any operation on the alarm host, the sound could be a fault detected by the alarm host. Please check further indication of the fault and solve it.
6.The alarm host connects to the external alarm horn, but when alarm goes off, the external alarm horn does not make sound.
Possible causes: the positive and negative wire between the horn and the host is opposite. There is short circuit or open circuit of the host and horn link. The host output voltage is not enough (about 12V). The external alarm horn is not programmed or correctly programmed into the alarm horn.
Solution: Check whether the wire connected to the alarm host and horn is correct. When the host is alarming, test the host’s external alarm interface voltage and it should be 12V or above. If there is no output, that means the external horn is not programmed or PGM output is not open. If the above operation is correct and still no sound from the alarm horn, then please replace a horn and test.
7.The alarm host does not dial telephone phone or mobile phone to notify the alarm.
Possible reasons: telephone line interference is too large, telephone line short circuit or open circuit or telephone anti-theft is turn on. The phone number is not programmed or correctly programmed to the alarm host. (including communication phone number, format, report level such as alarm report, fault report).
Solution: check whether the telephone line interference is too large, check whether the telephone line has a short circuit, open circuit problem exists, confirm whether the connected host’s telephone line needs to dial code before dialing the outside line phone. if need, please enter the code before the telephone number. Otherwise re-program the alarm receiving number correctly.

8.The alarm host does not communicate with service center after alarm.
Possible causes: Large interference of the telephone line caused the failure of data transmission. The host connected telephone line short circuit, open circuit. Programming process wrong of service center communication telephone number, communication format, communication level, user number etc.
Solution: Check whether the telephone line is short-circuited, open circuited. Correctly program the central communication telephone number, the central communication level, the central communication format, the user number. If all of the above is normal large telephone line interference maybe the cause. The central communication is a data transmission, different from the general voice transmission, if the telephone line interference is too large it will lead to unreliable communication. The engineer can do the following process to tests.
1.Listen to the telephone receiver, if there is a significant noise, you should find the communication company to solve it. Because the telephone line interference will cause the alarm host data transmission error.
Use a multimeter DC voltage range to test the following parameters for telephone lines
a. Empty voltage: When the telephone handset is not picked up, measure the DC voltage on the telephone line to see if it is 43 to 53 volts.
b. Pick up voltage: Pick up the telephone handset, measure the voltage on the telephone line, to see if it is 6 to 10 volts.
C. the resistance voltage: Parallel a 300 ohm resistor on the telephone line, measure the DC voltage on the telephone line to see if it is 6 to 12 volts.
After testing, do the following based on the test results:
a. If all the voltages tested meet the requirements, the line is OK and the alarm host should be replaced for a try. (The replacement alarm host must has been actually tested to the center communication and is very reliable, otherwise it may cause misjudgment)
b. If the voltage is not normal, but deviation is not much, you can series a 100, 200 or 300 ohm (1/4 watt) resistor on the telephone line to try it;
c. If the voltage is not normal and exceeds too much, or if the test according to B method does not solve the problem, please send the host back to our company together with the parameter records of the test. Our technical engineers will specifically modify the host circuit parameters according to the user’s phone line parameters to accommodate the telephone line.

Thirdly, detector failure
1. Beams
a. After the infrared beam is connected to the host and the host is armed, trigger the beam, but the alarm host does not alarm.
Possible causes: there are blocks between the two beams; the beam and the host connection is wrong; the beam tamper switch is not closed; the line has a short circuit, open circuit, insufficient supply voltage, beam zone properties are not programmed correctly.
Solution: correctly connect the line and end resistor between the beam and the alarm host (the connection and size of the resistor depends on the host used), check the line for short circuits, open circuit, test whether the power supply voltage of the beam is larger than 9V, check whether the alignment light on the transmitter end is off. Flashing or long light of the transmitter is not normal, reprogram the beam’s zone properties correctly.
b. During the initial installation and debugging of the beams, the alarm goes off when the alarm host is disarmed.
Possible cause: The beam is with open circuit and the zone property is set to a 24-hour zone.
Solution: Check the beam circuit and correctly connect it.
c. Why is the alignment light of the beam flashing or keeping on?
Possible causes: the synchronization wire connection is wrong, the receiving end and the transmitter end are not aligned, the receiving end and the transmitting end distance is too far, there are blockers in the detection area, the supply voltage is insufficient, the receiver’s tamper switch is not closed.
Solution: Correctly connect the synchronization wire; Check whether the tamper switch is closed; Adjust the angle between the receiving end and the transmitter to align it; Ensure that the supply voltage is above 9V.
d. The beam false alarm
Possible causes: the power supply voltage floating up and down too large, environmental causes. Intermittent short circuit caused by wire flooding.
Solutions: Ensure that the supply voltage is above 9V; Check whether the wiring is normal. Replace the false alarm beam with the correctly working alarm beam to check whether there is environment interference.

2. Detectors (wired, wireless)
a. After the detector is connected to the alarm host and the host is armed, trigger the detector, but the alarm does not goes off. Or the alarm host can not be armed caused there is zone error.
Possible causes: Wired detector and alarm host connection wrong; detector tamper-resistant switch is not closed; There is short-circuit or open-circuit; The supplied power is insufficient; The detector or the zone property is not correctly programmed.
Solution: correctly connect the wire and end resistor between the detector and the host (the connection and size of the resistor depends on the host used), check the line for short circuits, open circuit, test whether the supply voltage of the detector is larger than 9V. Check whether the detector alarm light is off when the tamper-resistant switch is closed. Reprogram the zone properties of the detector correctly.
b. During the initial installation and debugging of the detector, the alarm goes off when the alarm host is disarmed.
Possible cause: The detector is with open circuit and the zone property is set to a 24-hour zone.
Solution: Check the detector circuit and correct it.
c. False alarm of the detector.
Possible causes: Passive detector is used to detect changes of environmental temperature difference and makes alarm, sensitivity adjustment is not correct, detection of environmental temperature difference changes may lead to false alarm.
Solution: Check whether the line is intermittent short circuited caused by water. Adjust sensitivity and installation position appropriately. Check whether the supply voltage deviation is too large, replace the false alarm detector with the good detector to check whether it is the environmental cause.
d. After the wireless detector is installed, arm the alarm host and trigger the detector, but the alarm host does not alarm.
Possible causes:Low battery power, incorrect or no wireless code is registered. Incorrect or no program for the zone property during programming.
Solution: Ensure that the battery voltage is correct. If not, replace the battery. Re-code the wireless detector and program the zone properties.
e. the detector’s trigger light flashes, and the host also emits a fault chime?
Possible cause: The wireless detector battery is low.
Solution: Replace the detector battery.

3.Wireless door magnetic contact
The wireless door contact is installed and alarm host is armed, but it does not alarm after the door contact is triggered.
Possible causes: Low battery power, incorrect or no programming wireless code, incorrect or no programming for the zone property during programming.
Solution: Check that the battery voltage is correct, replace the battery if not normal, re-code the wireless door magnet and zone properties programming.
b. Why is the wireless door magnetic contact makes false alarm?
Possible cause: The mounting gap between the magnet and the motherboard is at the alarm edge.
Solution: The installation gap between the magnet and the motherboard is best not to be greater than defined. Adjust it according to the gap fluctuation of the installed position.
More News
The difference between loop control and direct control in automatic fire alarm system
The importance of intelligent security system management software
Common wired security alarm system working principle
Key points for the installation of various detectors
Enhance security of public places security
Linear infrared beam smoke detector
Wireless fire alarm linkage system
Residual current electrical fire detector
Simple and effective perimeter security equipment
Wire multiple detectors to one wired zone
Smart home and safe home
Outdoor perimeter security solutions
How to install professional alarm system
Fire fighting gas extinguish
Combustible gas alarm
Combustible gas detection
Carbon monoxide detection system
Fire alarm system input module
Fire alarm manual call point and hydrant button
Fire alarm Bus loop short circuit isolator module
Division of fire alarm areas
OVERVIEW OF AUTOMATIC FIRE ALARM SYSTEMS
Fire alarm system fire graphic display device
Fire alarm system fire control panel types
Addressable fire alarm bus loop
addressable fire alarm system loop
Linkage fire alarm system parts
Fire alarm linkage smoke exhausting
Independent electric fire detection system
ELECTRIC FIRE TEMPERATURE DETECTORS
division of fire alarm area
Selection and requirements of fire alarm control system
LINKAGE OF GAS FIRE EXTINGUISHING SYSTEM WITH FIRE ALARM
Wiring and principle of wired detector
WHY CAN SOLAR WIRELESS BEAM INCREASE SECURITY
Precautions for RS485 wiring
Why is electrical fire monitoring system needed
Program Beam sensor before installing
Guidance to shop solar wireless security system
Driveway Alarm System
How to test and install solar beam system
Perimeter security should be included in home security system
Perimeter security solution
Install Infrared Beams Detector
Can solar beam be used at gas station or oil depots
Improvement of active infrared detector
Types and features of outdoor security equipment
Security Solution for community safety
Plant area perimeter security solution
Questions of solar beam systems
Automatic fire alarm system and linkage
combustible gas detection is a subsystem
Prevention of fire and carbon monoxide poisoning
Don’t forget home security on Christmas and New Year
Precautions for use of fire alarm facilities after flood
LoRa intelligent wireless fire alarm system
Technical code for fire alarm system in wireless networking
What are the components of the automatic fire alarm system
Replace smoke alarms in time to avoid fire disasters
Gas fire extinguishing controller
Photoelectric beam smoke detector
Wireless fire alarm system
A life-saving smoke alarm in a fire
The three elements of Security Precaution
Alarm System Linkage
Do not use water for these types fire extinguishing
Loss free new anti theft alarm device
Combustible gas toxic gas monitoring system
The different security needs of shops with different size
Security alarm in intelligent parking lot
Linkage of burglar alarm and video surveillance system
Security service management platform
CO carbon monoxide detector
How to set up fire security system
Bus code fire control detector and module
Smoke detector types and application
Smoke detectors types and wiring
How to DIY home security
Fire alarm system types
Lower explosive limit of combustible gas
Home Security Fire Alarm and fire fighting
Connect solenoid valve with gas detector
How to design a 1000 channel large-scale monitoring system
How does the access control system link up with fire alarm and surveillance
Debugging of automatic fire alarm system
Home security solution
Why choose TCP/IP RJ45 network alarm control panel?
Integration of security system
Fire alarm system troubleshooting
Security industry development stages
https://vedard.com/blog/conventional-fire-alarm-system-is-suitable-for-small-places/
Setting and Debugging of automatic fire alarm system
https://vedard.com/blog/what-are-the-components-of-the-automatic-fire-alarm-system/
Analysis and solution of false alarm problem
China Top ten brands of burglar alarm system manufacturers
Why is electrical fire monitoring system needed
Training for installing fire alarm system
https://vedard.com/blog
How to build up security service center
How to minimize latency of monitoring systems
Surveillance alarm troubleshooting
What type smoke alarm is better
Difference of sound light alarm and explosion proof alarm
Smart fire alarm system
How to choose active infrared beams
China Security Exhibition 2019 Oct. 28th to 31st
Shopping mall and market interconnection security solution
Intelligent optical fiber perimeter security system
Garden solar alarm lamp
China Chemical plant explosion and Security Consideration
Fire and Explosion in Chemical Plant causes and prevention
Chemical plants fire escape methods and points for attention
Fire Alarm and automatic panel operation training
China Chemical plant explosion and Security Consideration
FIRE DETECTION & ALARM FOR PUBLIC BUILDING AND PREMISES
COMPLETE HOME SECURITY SYSTEM SELF-MONITORED
THEFT & BURGLAR ALARMS FOR HOME SECURITY
What to do with Fire alarm and How to recover alarm devices
How to install PIR and Door Contact for home security
7 causes for false alarm of fire detectors
PIR Passive Infrared Detector installing notice
Automatic fire alarm system terms of manual and automatic control
Is Burglar Alarm System useless?
6 home security solution for different budget and security levels
Electric Fire and Electric Socket
Security Service Network Alarm System upgrade
Explosion proof Fire Alarm Gas Detector Sounder Beacon
Solar Wireless PIR Detectors Features
Fire Alarm System Troubles Resolve Solutions
Fire Alarm Systems Maintenance and trouble shooting
How to avoid CO carbon monoxide poisoning
What is beam system and how does it work
Customers frequently asked questions about Solar Beam systems
How to clean Smoke Detector
Test Method and Notes for the Solar Powered Wireless Beams
Do not use water for these types fire extinguishing
How to disable Smoke Alarm temporarily?
Professional Security System installation standards
Home Security anti-theft knowledge and technology
How to escape from bus fire
How to use fire extinguishers
Flammable gas alarm installation and inspection
Addressable Fire Alarm System illustration
Building Fire Security System
Christmas Home Security Protection cautions
COMPLETE HOME SECURITY SYSTEM SELF-MONITORED
THEFT & BURGLAR ALARMS FOR HOME SECURITY
Wireless Fire Alarm System for commercial security
2017 China Security Fair News
Installing outdoor security cameras
Is Smart Home equal to App controlled Home
2017 China Public Security Exposition & Security Forum
Notice for wiring FC-7448 bus-line alarm system
How to install and debug FC-7448 Commercial Security Alarm System
2017 China Public Security Exposition
Combination of fingerprint lock and home security system
Cold Storage needs fire alarm system
Fire Security for garage, motor repair shop, parking area
FAS design notice
Photoelectric Beam Detection System Solution
How is sensor important for smart home
How to set up driveway alarm systems
Install intruder detector
Upgrade of PSTN network alarm service center
CMS server requirement and operation
meian tech wireless motion detector
Intrusion detector technology and development
intelligent security
Wireless fire alarm system
General Operation of Fire Alarm Control System
Addressable FACP MN300 Instruction
Alarm System Troubleshooting–Part 1 CMS
Alarm System Troubleshooting–Part 2 Alarm Control Panel
Alarm System Troubleshooting–Part 3 Detector
New technology security alarm server EAVS
Fire alarm system design
bus system security alarm technology
Fire Detectors types and selection
Exterior Security Protection
Home Incidents Prevention
Dangerous gas leakage Alarm Device Installation
Hotel Security Solution
Burglar Alarm System Installation Notes
Intelligent Community Security FAQ
Fire Indication on Alarm Control Panel
Fire Defighting System
Fire prevention and escape
Base Station Integrated Security Solution
Community Security Solution
October 25-28, 2016 China Security Exhibition
China Security Alarms Technology
Theft & Burglar Alarms for Home Security
Install Infrared Beams Detector
China Security Alarms Technology
Security System and Smart Home
Home Fire Prevention in Summer
Set up IP camera for home surveillance
Home Security Systems company Karassn cooperation
Pet immune Motion Detectors and the technology
How would you like to manage home security
Program Alarm Systems Solar Beam Detectors
Smoke Alarm types and connection
Question of Focus Security Alarm Systems
Security Alarm Systems Technical Supports
Security Service & DIY home security
Fire Alert Security Alarm Solution Signal Systems
Security Exhibition 2015 in Shenzhen China from 29th Oct.
Advanced Technology Burglar Alarm Systems
Install wireless door magnetic alarm sensor for rolling door
Fire guard read fire alarm manuals and test fire alarm systems before fire happening
Correct wiring Smoke Alarms for Fire Alarm systems
Carbon Monoxide danger
Questions for Solar-powered wireless infrared grating
Smoke Alarm Questions
Alarm system industry trend and alarm system installer job
Conventional Fire Alarm Security Solution
Perimeter Security Solution with Solar Beams
Reliable Wireless Alarm Systems
Smart Home & Secure Home
Flammable gas alarm installation and inspection
Program Alarm System and understand the terms
2014 Security China International Exhibition
Test Method and Notes for the Solar Powered Wireless Beams
Energy saving theft deterrent
Wireless Fire Alarm Solution For Hotel
Additional wireless detectors to existing alarm system
Home Alarm Security Service Development and the importance
Cheap or Quality China Alarms System
DIY alarms or Professional installed alarms
We help buyer buying China Alarm Security Systems
Alarm System Store for DIY without any consultant's advice
Cooperate with Alarm Systems Installers and Security Service
Digital Network Video Server alarm panel
Quick guide to program FC-7448 building security alarm panel
How to choose Motion Sensors from technology views
Advanced technique of intruder detectors
Integration of Security System
Wireless compare with Wired Alarm System
https://www.asmag.com/project/resource/index.aspx?aid=16&t=secutech-made-in-taiwan-products-and-solutions