https://www.asmag.com/showpost/35280.aspx
Product Info
The eLAN 2-Loop Lite Fire Alarm Panel

The eLAN 2-Loop Lite Fire Alarm Panel

MFNE
Region: Taiwan
Update: 05/28/2007
Key Specifications
STANDARD FEATURES (VF1000)

 Multi-loop (2); analog-addressable

 127 primary points per loop - 254 primary points per panel

 Network up to 127 nodes uses standard, Cat 5 Cabling

 Auto-learn capabilities

 Configurable through keypad or remotely, via eSP

 Programmable outputs on SLC loop

 Programmable Function button on front display

 Fire Drill button on front display

 5 Programmable Relays

 3 Programmable Inputs

 Day and night sensitivity settings

 LCD Display: 8x40

 Programmable Notification Circuits: 2

 Outputs programmable as Continuous, March, Temporal

 Zones: 500

 Program as AND, OR, or Any Two (Cross Zone)

 Access levels: 3

For more product information, please visit company''s website at www.vikingservnet.com