HS53 Smoke & Heat Detector
Shenzhen P&H Electronic Co., Ltd.
Region: China
Update: 05/09/2012
Key Specifications
HS53P-2 2 Wire Smoke & Heat Detector
HS53P-4 4 Wire Smoke & Heat Detector
Features
Designed to comply with UL539 standards
2 wire or 4 wire optional
Fixed temperature 57oC,135F heat sensor
Non-polar power input
Extended warranty
Easy Installation and maintenance
Characteristic
Dual LEDs for 360*degree visibility
Twist-off mounting for fast installation
Specifications
Model HS53P-2 HS53P-4
Operating Voltage DC9~35V
Standby Current 300uA
12mA(NC), 2mA(NO)
Alarm Current 18mA@DC12V;42mA@DC24V 4mA(NC), 15mA(NO)
Alarm Output Conventional Output & LED Flash Relay output (N.O/ N.C) and LED flash
Smoke Alarm Density 2.06%/ft
Alarm Temperature 57oC (135F)
Detecting Area 80 square meter (with the installation height of 6m-12m), and 60 square meter (with the installation height less than 6m)
Installation Method Ceiling Mounted
Operating Temperature -10°C ~ +55°C
Operating Humidity ≦95%RH
Dimensions 100mm(Dia)x48mm(H)